1. Process gain determines direction and magnitude
For a steady step, ΔPV = Kp × ΔCO. If the gain or step is negative, the response moves in the opposite direction; if either is zero, there is no modeled response.

Interactive engineering visualization
Change one parameter at a time. Watch the predicted process-variable deviation respond to a synthetic controller-output step. This is an open-loop FOPDT demonstration, not a closed-loop PID tuner or an equipment interface.
For a steady step, ΔPV = Kp × ΔCO. If the gain or step is negative, the response moves in the opposite direction; if either is zero, there is no modeled response.
Until time stepAt + θ, this idealized PV deviation stays zero. A sensor filter or transport delay can appear as effective delay in a fitted model.
One τ after the response starts, an ideal first-order process has completed about 63.2% of its total change. After five τ it is about 99.3% complete.
Engineering safeguard: Never infer a safe field test, controller action or valve fail position from this model alone. All results here are synthetic and ungraded.