These datasets are generated examples for education. They are not customer plant data, certified templates, or instructions to change a live controller.
Owned cases
60
Difficulty
20 intro · 20 intermediate · 20 advanced
Coverage
12 cases per loop family
introflowfundamentalsexpected: fit
Flow 01 — clean fast loop
Clean liquid-flow step test with a short lag and little dead time.
Establish the basic historian-to-FOPDT workflow and compare identified Kp, tau, and theta with known ground truth.
Load in LoopIQ IdentifyFormat: t,pv,op — the same synthetic fixture can be worked like a historian export.
Known ground truth: Kp=1.4, τ=6s, θ=1s · expected identification outcome: fit · LoopIQ-owned synthetic generator · redistributable: yes.
Step 2 · Start from an existing tuning
Change the baseline gains and see what they do
Step 3 · Ask LoopIQ for a published tuning rule
Kc
2.143
Ti (s)
6.000
Td (s)
0.000
Step 4 · Simulate before vs. recommended
See how the loop response changes before touching a controller
━━ Current/baseline━━ Recommended simulation
Rise time
— → 5.10 s
Settling time
60.00 s → 8.10 s
Overshoot
0.00% → 5.85%
IAE
22.00 → 2.24
ITAE
467.83 → 7.57
Step 5 · Understand the result
Translate the numbers into engineering meaning
Establish the basic historian-to-FOPDT workflow and compare identified Kp, tau, and theta with known ground truth.
The selected flow 01 — clean fast loop uses a synthetic FOPDT model with Kp=1.4, τ=6s, and θ=1s.
SIMC recommends Kc=2.143, Ti=6.000s, Td=0.000s for this training model.
In the simulator, settling changes from 60.00 s to 8.10 s, while overshoot changes from 0.00% to 5.85%.
The IAE changes from 22.00 to 2.24. Lower is generally better for this specific simulated step, but a real plant decision still requires process knowledge, constraints, and supervised validation.
Training rule: simulated improvement is evidence about this model only. A real loop change should be reviewed against process constraints, operating state, alarms/interlocks, actuator limits, and site procedures, then validated under supervision.
Keep learning after your first exercise
These optional lessons and examples support safe simulation and engineering judgment. Start with the practice above.
All 60 native cases are LoopIQ-owned synthetic FOPDT examples, spanning five loop families and three difficulty levels. They are ungraded practice and do not award credentials or write assessed progress.
Download a case CSV and load it into LoopIQ Identify to compare the fitted model against known ground truth. This Lab never connects to or writes to a live controller.
The separate extended simulator offers 84 exercises and four model families, with device-local practice history. Its records remain separate from the protected Competency Lab.